Outdoor Vacuum Circuit Breaker

High Voltage Element

ZW32-24(G) Outdoor vacuum circuit breaker

Classification Series :Outdoor Vacuum Circuit Breaker
Product Name :ZW32-24(G) Outdoor vacuum circuit breaker
Product Overview
ZW32-24 series outdoor pole mounted high voltage vacuum circuit breaker is used as the main control and protective equipment in three phases power system of AC50Hz, voltage 24KV to switch on/off loading current overloading current and short circuit current

▸ Product Introduction

Description

ZW32-24 series outdoor pole mounted high voltage vacuum circuit breaker is used as the main  control and protective equipment in three phases power system of AC50Hz, voltage 24KV to switch on/off loading current overloading current and short circuit current, it applies to distribution system of substation, industrial enterprises to control and protect the downstream equipment.

The breaker adopts vertical column, dry structure, it has function of reliable  insulation, long electric life and free maintenance. It is specially used  for places where it needs frequent operation and rural network where has little  maintenance services.


Standards Compliant

GB1984 AC high voltage circuit breakers"

GB11022 "high-voltage switchgear and control equipment standards commontechnical requirements"

GB311.1-6 "insulated high voltage transmission and distribution equipment."

GB763 "AC high voltage electrical heating during long-term work"

GB2706"AC high voltage electrical dynamic and thermal stability test methods"

GB3309 high voltage switchgear at room temperature mechanical test"

DL/T593 "common ordering technology high voltage switchgear


Model description

0


Environmental conditions

1.ambient air temperature:+40℃~-40 ℃

2.a height of not more than 2000 meters above sea level

3.the wind speed is not greater than 35m/s

4.anti-contamination level for grade IV

5.the earthquake intensity does not exceed 8 degrees

6.no fire,explosion,severe chemical corrosion of the place


Technical Data

1Rated voltageKV24
2Rated insulation level1 min withstand voltage (Dry)65/65
1 min withstand voltage (Wet)50
Lightning impulse withstand voltage (peak)125/145
3Rated frequencyHZ50
4Rated currentA630, 1250,1600
5Rated short circuit breaking currentkA20, 25, 31.5
6Rated short circuit making current (peak)kA50, 63, 80
7Rated short time withstand currentkA20, 25, 31.5
8Duration rated short circuit currentS4
9Nos of breaking rated short circuit breaking currentTimes30
10Fixed operation sequence
off-0.3S-on/off-180S on/off
10Opening timems18-45
11Closing time25-60
121min secondary circuit power frequency withstand voltageV2000
13Polar distancemm395±2
14Mechanical lifeTimes10,000
13Rated operating voltage and rated voltage of auxiliary loopVAC/DC220, 110; DC24
16Contact open distance  mm12 ±1
17Contact Over-travelmm3±1
18Average opening speed  m/s1.1±1.7
19Average closing speed  m/s0.5-1.0
20Three phase simultaneity          ms≤2
21Contact closing bounce time  ms≤2
22Main circuit DC resistance per phases μΩ≤100