SF6 Circuit Breaker Series

High Voltage Element

ZCW-72.5/126.5 Open-air high-voltage assembly switchgear

Classification Series :SF6 Circuit Breaker Series
Product Name :ZCW-72.5/126.5 Open-air high-voltage assembly switchgear
Product Overview
The circuit breaker, disconnecting switch, grounding switch, current transformer, busbar, and other components are organically combined on a grounded steel frame, resulting in a compact structure. It occupies only 30%-50% of the space compared to a separate-type configuration...

▸ Product Introduction

Structural Features

The circuit breaker, disconnecting switch, grounding switch, current transformer, busbar, and other components are organically combined on a grounded steel frame, resulting in a compact structure. It occupies only 30%-50% of the space compared to a separate-type configuration, offering significant advantages such as land savings and reduced construction costs.

The entire compartment is prefabricated in the factory, with assembly and all commissioning completed before shipment, allowing for transportation as a complete unit to the installation site. This greatly shortens the installation period. The design utilizes highly proven, high-performance arc-extinguishing chambers and disconnecting switches, which require minimal maintenance and have high reliability.

The self-supporting busbar, prefabricated in the factory, eliminates the need for the user to build a frame. The layout is flexible and can accommodate various wiring configurations. The circuit breaker can be fully lowered for maintenance or replacement. In the event of a failure, the downtime can be reduced to less than 3 hours, minimizing power outages.


Main Technical Parameters of Circuit Breaker

No.

Name

Unit

Parameter

1

Rated voltage

kV

72.5

2

Rated power frequency withstand voltage (1 Minute) – Grounded

kV

160


Rated power frequency withstand voltage (1 Minute) – Contact gap

kV

200

3

Rated lightning impulse withstand voltage – Grounded

kV

350


Rated lightning impulse withstand voltage – Contact gap

kV

410

4

Power frequency withstand voltage of SF6 gas at zero gauge pressure (5 min)

kV

84

5

Rated frequency

Hz

50

6

Rated current

A

3150

7

First level coefficient


1.5

8

Rated short-circuit breaking current

kA

31.5

9

Rated short-circuit making current (peak value)

kA

80

10

Rated short-circuit withstand current

kA

31.5

11

Rated peak withstand current

kA

80

12

Rated short circuit duration

s

4

13

Rated out of step breaking current

kA

8

14

Short-range fault breaking current

kA

90%Ik, 75%Ik

15

Rated line charging switching current

A

10

16

Rated operating sequence


0-0.3s-CO-180s-CO

17

Main circuit resistance

µΩ

≤ 40

18

Rated sulfur hexafluoride gas pressure (20°C gauge pressure)

MPa

0.5

19

Alarm/minimum function pressure (20°C gauge pressure)

MPa

0.45±0.03

20

SF6 gas annual leakage rate


<0.5%

21

Gas moisture content (V/V)


≤150×10⁻⁶

22

Mechanical life

Times

10000

23

Radio interference level

µV

≤500

24

Creep distance – Contact gap

mm

2585


Creep distance – Grounded

mm

2248

25

Weight of each unit filled with SF6 gas

kg

10

26

Weight of each circuit breaker

kg

1300


Tel
Fax
WeChat