SF6 Circuit Breaker Series

High Voltage Element

LW16-40.5 Outdoor SF6 circuit breaker

Classification Series :SF6 Circuit Breaker Series
Product Name :LW16-40.5 Outdoor SF6 circuit breaker
Product Overview
LW16-40.5 outdoor SF6 circuit breaker is designed for use in a 50 Hz three-phase AC power system and is suitable for control and protection in industrial enterprises, power plants, and substations. This product is capable of frequent operations and can be used as...

▸ Product Introduction

Product Introduction

The LW16-40.5 outdoor SF6 circuit breaker is designed for use in a 50 Hz three-phase AC power system and is suitable for control and protection in industrial enterprises, power plants, and substations. This product is capable of frequent operations and can be used as a link circuit breaker and for switching capacitor banks or reactor banks. The internal current transformers can be used for measurement and protection. It can directly replace the SW2-35 oil circuit breaker and, with the addition of an overcurrent bracket, can replace various models of oil circuit breakers. It is an ideal oil-free circuit breaker for 35 kV power systems.

Note:

When the circuit breaker is in hot standby mode, surge arresters must be installed on the fault side of the breaker.


Main Technical Parameters of Circuit Breaker

No.

Parameter Name

Unit

Parameter Value

1

Rated voltage

kV

40.5

2

1-Minute power frequency withstand voltage

kV

95 (Grounded) / 185 (Contact gap)

3

Rated frequency

Hz

50

4

Rated current

A

1600, 2000

5

Rated short-circuit breaking current

kA

25 (reclosing), 31.5 (single separation)

6

Rated short-circuit making current (peak)

kA

63

7

Rated short-time withstand current

kA

25

8

Rated short circuit duration

s

4

9

Rated peak withstand current

kA

63

10

Rated operating sequence

O—0.3s—CO—180s—CO

11

Rated switching current for a single capacitor bank

A

400

12

Rated out-of-step breaking current

kA

6.3

13

Rated out-of-phase breaking current

kA

21.75

14

Mechanical life test

Times

3000

15

Rated cumulative breaking times (rated current)

Times

2000

16

Rated cumulative breaking times (25kA short-circuit)

Times

21

17

Tripping time

s

≤0.06 (rated/max voltage) / ≤0.10 (min voltage)

18

Closing time

s

≤0.15

19

SF6 gas rated pressure (20℃ gauge pressure)

MPa

0.60±0.015

20

SF6 gas refill alarm pressure (20℃ gauge pressure)

MPa

0.55±0.015

21

SF6 gas minimum functional pressure (20℃ gauge)

MPa

0.52±0.015

22

SF6 gas annual leakage rate

%/Year

≤1

23

SF6 gas trace moisture content

ppm (V/V)

≤150×10⁻⁶

24

CT14-A mechanism coil rated voltage

V

DC: 110/220; AC: 220/380

25

SF6 gas weight

kg

Normal: 2.5; CT: 6; Elevated CT: 8

26

Circuit breaker weight

kg

1000

27

External insulation leakage specific distance

mm/kV

≥31

28

Porcelain insulator leakage distance

mm

≥1255

Notes

O:Open operation 

CO:Close-Open operation 

s:Seconds 

ppm:Parts per million 

CT:Current Transformer configuration 


Formatting Consistency

Values with tolerances (e.g., ±0.015) and conditional parameters (e.g., reclosing/single separation) are explicitly stated.   

Units standardized (e.g., “kV” for kilovolts, “MPa” for megapascals).   

Scientific notation corrected (e.g., “≤150×10” instead of “X10-6”).   

Combined entries (e.g., tripping time under different voltages) are merged for clarity.