Indoor Vacuum Circuit Breaker

High Voltage Element

VEB-12 Indoor high voltage vacuum circuit breaker

Classification Series :Indoor Vacuum Circuit Breaker
Product Name :VEB-12 Indoor high voltage vacuum circuit breaker
Product Overview
Inlet/outlet protection of 12kV distribution system, core distribution station of industrial and mining enterprises, and high-voltage side of wind power/photovoltaic box transformer...

▸ Product Introduction

Model decoding

V: Vacuum.

E: design serial number (Evolution)

B: Breaker.

12: Rated voltage level (kV)


Core function

Full-condition protection: interrupting rated current, overload current and maximum 50kA short-circuit current.

Fast isolation: the opening time is ≤35ms, and the fault cutting speed is 20% ahead of similar products.


Typical application

Inlet/outlet protection of 12kV distribution system, core distribution station of industrial and mining enterprises, and high-voltage side of wind power/photovoltaic box transformer (suitable for cabinets such as KYN28A-12 and XGN15-12).


Technical parameter

Parameter

Unit

Standard value range

Peak capacity

Rated voltage (Ur)

kV

12

-

Rated current (Ir)

A

630/1250/1600/2000/2500

3150 (customized)

Rated short-circuit breaking current (Isc)

kA

20/25/31.5/40

50  (enhanced)

Rated short-term withstand current (4s)

kA

= Isc

-

Rated peak withstand current

kA

50/63/80

100

Dielectric level




Power frequency withstand voltage (1min)

kV

42 (alternate)/ 48 (fracture)

-

Lightning impulse withstand voltage (peak value)

kV

75 (alternate)/ 85 (fracture)

-

Mechanical properties




Opening time

ms

≤35

-

Closing time

ms

≤75

-

On-off time

ms

≤60

-

Mechanical life

Frequency

≥30,000

-

Rated current electrical life

Frequency

≥10,000

-

Full capacity breaking times (Isc=40kA)

Frequency

≥50

-


Intelligent control accessory

Operating power supply: DC 48V/110V/220V or AC 220V.

Communication protocol: RS485+Modbus is standard and supports IEC 61850-8-1 (optional).

Protection interface: 4× passive contact (on/off/energy storage/fault)


Key technical requirements for operation and maintenance

Mechanical characteristics monitoring:

Warning value: brake opening speed decreases by > 15% or overtravel changes by > 2mm → trigger maintenance warning.


Periodic maintenance

3 years /5000 operations: measure the resistance of the main circuit (standard: ≤25μΩ @ 1250A).

10 years: replace vacuum interrupter (depending on wear monitoring data)


Safety interlock

Forced locking logic: it is forbidden to operate the grounding knife switch when the circuit breaker is closed (in line with GB 3906 Five Preventions).