High Voltage Isolating Switch

High Voltage Element

GND5-12 Disconnecting switch

Classification Series :High Voltage Isolating Switch
Product Name :GND5-12 Disconnecting switch
Product Overview
GND5-12 disconnector has a novel structure. The static contact is installed on the insulator at the top of the cabinet, and the horizontal bus bar is directly connected to the static contact through the installation box

▸ Product Introduction

Product overview

GND5-12 disconnector has a novel structure. The static contact is installed on the insulator at the top of the cabinet, and the horizontal bus bar is directly connected to the static contact through the installation box, and the moving contact is installed at the incoming end of the circuit breaker.


Model decoding:

GN: Indoor Disconnector.

D: Rotary Blade

5: Design serial number

12: Rated voltage (kV)


Core function

Safety isolation: establish visible fracture to ensure maintenance safety.

No arc extinguishing ability: it is forbidden to operate with load!


Typical application

Bus isolation of 12kV switchgear and overhaul isolation of transformer incoming side (suitable for cabinets such as KYN28A-12 and XGN2-12)


Technical paramete

Parameter

Unit

Standard value

High altitude type

Rated voltage

kV

12

Rated current

A

630/1250

1600

Rated short-term withstand current (4s)

kA

20/25/31.5

40

Rated peak withstand current

kA

50/63/80

100

Dielectric level




Power frequency withstand voltage (1min)

kV

42 (to ground) / 48 (fracture)

Lightning impulse withstand voltage (peak value)

kV

75(to ground) / 85(fracture)

Mechanical properties




Closing torque

N·m

≤150

Opening torque

N·m

≤120

Mechanical life

Frequency

≥2000